Residential Electrical Inspection
Handout/Checklist
Generally, Alaska law requires all electrical work to be
performed by licensed, bonded and insured electrical contractors
or their employees.
- Homeowners, within strict limitations, are exempt from
electrical licensing.
- An owner may perform electrical installation on residential
property that is owned by the installer or a member of the
installer's immediate family and not intended for sale at the
time of making the installation.(AS 08.40.190)
- All wiring shall be inspected before it is concealed and the
installer shall notify the inspector when the wiring is complete,
before the wiring is utilized and the associated space
occupied.
A ROUGH-IN INSPECTION must be made before
insulation, sheet-rock, paneling, or other materials cover any
wiring. Underground wiring must be inspected before the trench is
back-filled. Except for the final connection to switches,
receptacles, and lighting fixtures, all ground wires and other
wires in boxes must be spliced and pigtailed for the rough-in
inspection!
PLAN YOUR WIRING
PROJECT
This brochure is intended to be a general
overview of residential electrical requirements. No claim is made
that this information is complete or beyond question. Additional
information and knowledge is needed to properly install
electrical wiring that is essentially free from fire and electric
shock hazard. For assistance, please reference authoritative
publications based on the 2005 National Electrical Code(the
NEC).
CALL OUR OFFICE AT
907-283-4732, IF YOU HAVE QUESTIONS.
General
Circuitry
NEC 210.11 and 422.12 In addition to the
branch circuits installed to supply general illumination and
receptacle outlets in dwelling units, the following minimum
requirements apply:
- Two 20-amp circuits for the kitchen countertop
receptacles
- One 20-amp circuit for the laundry receptacles
- One 20-amp circuit for the bathroom receptacles or entire
single bathroom including lights, exhaust fan, etcetera, if in
accordance with NEC 210.23(A)(1)and(A)(2).
- One separate, individual branch circuit for central heating
equipment
NEC 210.52 Receptacles installed in the kitchen to
serve countertop surfaces shall be supplied by not less than two
separate small appliance branch circuits.
NEC 300.3 All conductors of the same circuit,
including grounding and bonding conductors, shall be contained in
the same raceway, cable, or trench.
NEC 408.4 Every circuit and circuit modification
shall be legibly identified as to its clear, evident and specific
purpose or use in sufficient detail on a directory located on the
face or inside of the electrical panel doors.
NEC 240.3 Generally, the rating of the fuse or
circuit breaker determines the minimum size of the circuit
conductor, per the following table:
Fuse or Circuit Breaker Size
|
Minimum Wire Size
|
Copper Conductor
|
Aluminum Conductor
|
15 amps
|
14
|
n/a
|
20 amps
|
n/a
|
n/a
|
30 amps
|
10
|
8
|
40 amps
|
8
|
6
|
50 amps
|
6
|
4
|
Note: Conductors that supply motors, air-conditioning units,
and other special equipment may have over current protection that
exceeds the general limitations in the above chart.
NEC 406.3 Receptacle outlets shall be of the
grounding type, be effectively grounded, and have proper
polarity.
NEC 210.52 Generally, receptacle outlets in habitable
rooms shall be installed so that no point measured horizontally
along the floor line in any wall space is more than 6 feet from a
receptacle outlet. A receptacle shall be installed in each wall
space 2 feet or more in width.
NEC 210.52 At kitchen countertops, receptacle outlets
shall be installed so that no point along the wall line is more
than 24 inches measured horizontally from a receptacle outlet in
that space. Countertop & Island counter top spaces separated
by range tops, sinks or refrigerators are separate spaces.
NEC 210.52 A receptacle outlet shall be installed at
each counter space 12 inch or wider, and at each island counter
or peninsular space 24 inch by 12 inch or greater. Receptacles
shall be located not more than 20 inch above the countertop, or
where mounted below a countertop less than 6 inches beyond the
support base, not more than 12 inch below the countertop.
NEC 210.52 & 406.8 & 210.63 At least one
receptacle, accessible at grade level and no more than 6.5'
above grade, shall be installed at the front and back of a
dwelling and shall have (in-use) covers that are weatherproof
whether or not an attachment plug is inserted. Also if an outdoor
air conditioner unit is installed and it is not within 25 feet of
the required front or rear receptacles then it needs to have an
additional GFCI protected receptacle installed within 25 feet of
unit.
NEC 210.12 All branch circuits supplying 125-volt, 15
and 20 ampere outlets in dwelling unit bedrooms shall be
protected by a listed arc-fault circuit interrupter.
Ground-Fault
Protection
NEC 210.8 Ground-fault circuit-interrupter (GFCI)
protection shall be provided for all 125-volt, 15 and 20 amp
receptacle outlets installed outdoors, in boathouses, garages,
unfinished accessory buildings, crawl spaces at or below grade
level, unfinished basements, bathrooms, at kitchen countertops
and within 6 feet of the outside edge of all laundry, utility,
and wet-bars sinks.
NEC 680.71 & 110.3 A hydro-massage bathtub, (a
bathtub with a re-circulating piping system, designed to
discharge water upon each use) and its associated components
shall have ground-fault circuit interrupter protection. Also
needs to have a dedicated circuit based on the requirements
listed in the manufactures specifications. Note:( If the tub
has an in-line water heater installed it may require two
dedicated circuits)
NEC 680.71 All 125-volt receptacles not exceeding 30
amperes installed within 5 feet of the inside walls of a hydro
massage bathtub shall be GFCI protected.
NEC 680.73 Hydro massage bathtub equipment shall be
accessible without damaging the building structure or
finish.
NEC 682.33 All circuits rated not more than 60 amps
at 120 through 250-volts installed outdoors for equipment in or
adjacent to natural and artificial bodies of water shall have
GFCI protection.
Wiring
Methods
NEC 314.23 All electrical boxes shall be rigidly
secured to the building structure.
NEC 314.27 Boxes used as the sole support for a
ceiling-suspended paddle fan shall be listed and marked as
ceiling fan rated, and not be used for fans weighing more than 70
lbs.
NEC 334.30 Type NM (nonmetallic) cables shall be
secured at intervals not exceeding 4.5' and within 12 inch of
each box.
NEC 314.17 The outer jacket of NM cable shall be
secured to the box and extend into the box a minimum of 1/4
inch.
NEC 300.14 The minimum length of conductors,
including grounding conductors, at all boxes shall be 6 inches
with at least 3 inches extending outside the box.
NEC 300.4 Where cables are installed through bored
holes in joists, rafters, or wood framing members, the holes
shall be bored so that the edge of the hole is not less than 1
1/4 inch from the nearest edge of the wood member. If this
distance cannot be maintained, or where screws or nails are
likely to penetrate the cable, it shall be protected by a steel
plate at least 1/16 inch thick and of appropriate length and
width.
NEC 300.22 Type NM cable shall not be installed in
spaces specifically fabricated for environmental air, but may
pass perpendicular through joist or stud spaces.
NEC 110.14 Only one conductor shall be installed
under a terminal screw. Boxes with more than one grounding wire,
the grounding wires shall be spliced with a "wire tail"
or "pigtail" which is then attached to the grounding
terminal screw of the device.
NEC 110.14 Splices shall be made with an approved
splice cap or "wire nut" and shall be made in approved
electrical boxes or enclosures.
NEC 250.134 & 314.4 & 404.9 All electrical
equipment, metal boxes, cover plates, and plaster rings shall be
grounded. All switches, including dimmer switches, shall be
grounded.
NEC 110.12 & 314.17 Unused openings in boxes
shall be effectively closed. If openings in non-metallic boxes
are broken out and not used, the entire box must be
replaced.
NEC 408.41 Each grounded (neutral/white) conductor
shall terminate within a panel board in an individual terminal
that is not used for any other conductor.
NEC 200.7(C) Where permanently re-identified at each
location where it is visible and accessible, the conductor in
type NM cable with white colored insulation may be used as an
ungrounded (hot/phase) conductor.
NEC 314.25 & 410.12 In completed installations,
each box shall have a lamp-holder, canopy or device with an
appropriate cover plate.
NEC 314.9 Junction boxes shall be installed so that
the wiring contained in them can be rendered accessible without
removing any part of the building.
NEC 314.16 The volume of electrical boxes shall be
sufficient for the number of conductors, devices, and cable
clamps contained within the box. Non metallic boxes are marked
with their cubic inch capacity. Use the following table to
calculate each box size:
Conductor Size
|
14 AWG
|
12 AWG
|
Each separate insulated wire
|
2 cubic in
|
2.25 cubic in
|
All ground wires ( combined )
|
2 cubic in
|
2.25 cubic in
|
For each device ( switch/receptacle )
|
4 cubic in
|
4.5 cubic in
|
All internal cable clamps ( combined )
|
2 cubic in
|
2.25 cubic in
|
Example:
8 insulated wires
|
18 cubic in
|
All ground wires
|
2.25 cubic in
|
1 switch
|
4.5 cubic in
|
1 receptacles
|
4.5 cubic in
|
All clamps ( combined )
|
2.25 cubic in
|
Total Box volume required
|
31.5 cubic in
|
NEC 410.8 luminaries (lighting fixtures) installed in
clothes closets shall have the following minimum clearances from
the defined storage area (see below):
- 12 inch for surface incandescent fixtures (these fixtures
must be totally enclosed)!
- 6 inch for recessed incandescent fixtures (these fixtures
must have a totally enclosed trim Example: shower
trim).
- 6 inch for fluorescent fixtures.
NEC 410.8 Storage space, as applied to an electrical
installation in a closet, is the volume bounded by the sides and
back closet walls and planes extending from the closet floor
vertically to a height of 6 feet of the highest clothes-hanging
rod and parallel to the closet walls at a horizontal distance of
24 inches from the sides and back of the closet walls
respectively, and continuing vertically to the closet ceiling
parallel to the walls respectively, and continuing vertically to
the closet ceiling parallel to the walls at a horizontal distance
of 12 inches or the shelf width, whichever is greater.
NEC 410.8 Incandescent luminaries with open or
partially enclosed lamps and pendant fixtures or
lamp-holders are not permitted in clothes closets.
NEC 410.66 Recessed lighting fixtures installed in
insulated ceilings or installed within 1/2 inch of combustible
material shall be approved for insulation contact and labeled
Type IC.
Electrical
Services
NEC 310-15 CONDUCTOR SIZES FOR 120/240 VOLT 3-WIRE,
SINGLE-PHASE, DWELLING SERVICES AND FEEDERS:
Copper
|
Aluminum
|
Service Rating
|
4 AWG
|
2 AWG
|
100 amps
|
1 AWG
|
2/0
|
150 amps
|
2/0
|
4/0
|
200 amps
|
NEC 110.14 Listed anti-oxidant compounds shall be
used on all aluminum conductor terminations; unless information
specifically states that it is not required.
NEC 300.7 Portions of raceways or sleeves subject to
different temperatures (i.e. passing from the interior to the
exterior of a building) shall be sealed with an approved material
to prevent condensation from entering equipment.
NEC 230.54 Service entrance conductors shall be
rain-tight and arranged to drain.
NEC 300.4 Where raceways containing ungrounded
conductors No. 4 or larger enter a cabinet, box, or enclosure,
the conductors shall be protected by a bushing providing a
smoothly rounded insulating surface.
NEC 230.70 The service disconnecting means shall be
installed at a readily accessible location either outside a
building or structure or inside nearest the point of entrance of
the service entrance conductors.
NEC 230.70 & 240.24 & 110.26 Electrical
panels shall be readily accessible and shall not be located in
bathrooms, or in the vicinity of easily ignitable materials such
as clothes closets or in a basement or crawl space that has less
than 6 feet 6 inches of headroom from floor to ceiling.
NEC 408.36 Plug-in type over current devices that are
back-fed shall be secured by an additional approved device.
NEC 110.26 Sufficient working space shall be provided
around electrical equipment. The depth of that space in the
direction of access to live parts shall be a minimum of 3 feet.
The minimum width of that space in front of electrical equipment
shall be the width of the equipment or 30 inches whichever is
greater. This workspace shall be clear and extend from the floor
to a height of 6.5’. This space shall not be
used for storage.
NEC 110.26 Illumination shall be provided for all
working spaces about service equipment and panel boards
Grounding
NEC 250.50 All grounding electrodes that are present
at each building or structure served shall be bonded together to
form the grounding electrode system.
NEC 250.50 Permitted electrodes include:
- Metal underground water pipe in direct contact with earth for
10 feet or more
- Metal frame of the building or structure
- Concrete encased electrodes
- Ground ring
- Rod or pipe electrode
- Plate electrode
- Other metal underground systems or structures.
NEC 250.53 A metal underground water pipe shall be
supplemented by an additional electrode.
NEC 250.64 The grounding electrode conductor shall be
continuous, securely fastened and protected from physical
damage.
NEC 250.66 The size of the grounding electrode
conductor shall be determined by the size of the service-entrance
conductors, per the following chart:
Equivalent Size of Service
Entrance Conductor
|
Size of the Grounding Electrode
Conductor
|
Copper
|
Aluminum
|
Copper
|
Aluminum
|
4 AWG
|
2
|
8*
|
6
|
1 AWG
|
2/0
|
6
|
4
|
2/0 or 3/0
|
4/0 or 250
|
4
|
2
|
*The conductor that is the sole connection to
a rod, pipe or plate electrode is not required to be larger than
#8 AWG copper, however conductors smaller than #6 AWG require
physical protection. *The conductor that is the sole connection
to a concrete encased electrode shall not be required to be
larger than #4 AWG and must be copper.
NEC 250.28 A main bonding jumper or the green bonding
screw provided by the panel manufacturer shall be installed in
the service panel.
NEC 250.104 The interior metal water piping and other
metal piping that may become energized shall be bonded to the
service equipment with a bonding jumper sized the same as the
grounding electrode conductor.
Underground
Wiring
NEC 300.5 Direct buried cable or conduit or other
raceways shall meet the following minimum cover
requirements:
Direct Burial Cable
|
Rigid or
Intermediate
Metal Conduit
|
Non Metallic
Raceway (PVC)
|
24"
|
6"
|
18"
|
Residential branch circuits rated 20 amps or less at 120 volts or
less and with GFCI
protection at their source are allowed a minimum cover of
12"
|
NEC 300.5 Underground service laterals shall have
their location identified by a warning ribbon placed in the
trench at least 12" above the underground
installation.
NEC 300.5 Where subject to movement, direct buried
cables or raceways shall be arranged to prevent damage to the
enclosed conductors or connected equipment.
NEC 110.14 Wire splicing means for direct burial
conductors shall be listed for such use.
NEC 300.5 Conductors emerging from underground shall
be installed in rigid metal conduit, intermediate metal conduit,
or Schedule 80 rigid nonmetallic conduit from 18â€
below grade or the minimum cover distance to the point of
termination above ground.